By pointing the mouse to any bar, the corresponding tap statistic will be
highlighted as well as displayed in a tool tip.
4.10.4.5
Real Time Voltage Chart
The Real Time Voltage Chart feature allows the user to monitor in real time the last 60
seconds of the source voltage value and load voltage. The Voltage Chart freezes the last
30 seconds of the voltage profile and displays the current values.
GUID-9DB711F5-2328-42EE-A564-6C63AD18201A V1 EN
Figure 108:
Real Time Voltage Chart
4.10.4.6
Harmonic Analysis
The input signal is sampled at 64 samples per cycle, giving an overall sampling rate of
3840 samples per second for a 60 Hz system. This provides the ability to reproduce signals
of up to 1920 Hz. Therefore, up to the 31st harmonic can be calculated using discrete
Fourier transform with a fundamental frequency of 60 Hz. The fundamental for both the
Voltage and Current channels is calculated every sample meaning, every 260.41 μs. These
Section 4
1VAC388793-MB A
TCC600
166
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......