TCC600 Reverse Power Vendor Cross Reference
The Reverse Power section of the TCC600 Setpoints screen also contains a link which
displays the "Reverse Power Vendor Cross Reference" table showing Cooper/Siemens
reverse power names and their ABB equivalents.
GUID-F94E7F6F-8790-48D5-8849-51B45512FDBC V1 EN
Figure 420:
TCC600 Reverse Power Vendor Cross Reference Table
7.6.1
Setting Reverse Power Operation and Power Direction Bias
Mode from the HMI
1.
Press the Up Arrow (SETP Hot Button) pushbutton to wake the unit. The menu will
advance to "SETPOINTS".
2.
Press the Down Arrow pushbutton once. The unit will display the following:
Profile Settings
3.
Press the Right or Left arrow pushbuttons, as necessary, to navigate to the "Common
Settings" menu.
Editing Setpoints in the wrong Setpoint Profile can cause the control
to operate incorrectly.
4.
Verify that the desired Setpoint Profile is indicated, then press the Down arrow
pushbutton, as necessary, to navigate to the "Rev Power Operation" menu item.
Section 7
1VAC388793-MB A
Setpoints
530
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......