1. Individual not duplicated communications address (0x212)
2. Feeder address = 0x4003
3. Substation address = 0x5001
In order to poll D1 on an individual basis address, 0x212 is used.
To invoke for example, voltage reduction individually on D1, use direct operate with or
without acknowledge for address 0x212 on the appropriate point.
To invoke voltage reduction on Feeder F4, use direct operate without acknowledge to
address 0x4003 instead of 3 different commands sent to D1, D2 and D3 individually.
Similarly, invoking voltage reduction on an entire substation requires a direct operate
command without acknowledge to be sent to that substation address e.g. substation S2
( address 0x5001).
1VAC388793-MB A
Section 5
System setup
TCC300
281
User Manual