6.2.5.2
Setting Input Selection 1 Operation Counter Input Configuration to Motor
Seal-In from TCC600
If Tap Information is selected to either "Contact KeepTrack 1R1L" or
"Contact KeepTrack 1N" the control will not accept an Input Selection 1
setting of "Seal-In Input". TCC600 will display the Tap Information/Input
Selection Error Screen if applicable.
GUID-B6D4D46A-325E-40E8-98DC-360F2D08C41C V1 EN
Figure 275:
Tap Information/Input Selection Conflict Error Screen
1.
Select
Setup/Configuration
from the TCC600 toolbar. TCC600 will display the
Tap Configuration dialog screen.
1VAC388793-MB A
Section 6
Configuration
TCC300
351
User Manual