File - New, Open, Save Template, Save, Save As
•
Schema - 1.4 or 3.0
•
Reporting - Metering Dataset and Status Dataset
•
GOOSE Publisher - 1 through 5
•
GOOSE Subscriber - 1 and 2
•
Validate • Print and Print Preview
•
See Appendix D for detailed information
Also, the IEC 61850 menu provides access to "Send" and "Receive" Configuration Files,
CID File Identifier and the Non-Standard Data Definition document (.pdf) for reference.
Sending IEC 61850 configuration files
1.
Start the TCC600® Communications Software on the PC.
2.
Connect to the TCC300 control.
3.
Select
Utility/IEC61850/Configuration File/Send
. TCC600 will display the
"Authentication Key Generated Successfully" confirmation screen.
GUID-05A47015-EBDE-4BE3-B4DA-60BA37437FC2 V1 EN
Figure 159:
Authentication Key Generated Dialog Screen
4.
Select
OK
. TCC600 will display the "Open" dialog screen with a default file
extension of "*.cid".
5.
Select the desired Configuration file, then select "Open". TCC600 will display the
"Send" status screen while the Configuration file is sent.
Section 4
1VAC388793-MB A
TCC600
228
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......