UDP Port Settings
A total of 5 UDP channels exist for DNP. The first channel is reserved for unsolicited
messages. The control will send any unsolicited responses to the UDP Remote IP/Port that
has been configured. If the Remote IP and Port have not been configured, the unit will not
send any unsolicited messages.
GUID-10682DFF-292E-4E82-8FD0-AEC80331CB5A V1 EN
Figure 168:
UDP Settings Dialog Screen
Uploading DNP configuration files
1.
From the TCC600® Main Screen select
Utility/DNP/Send DNP Configuration
File
. TCC600 will display the Authentication Key Generated dialog screen.
GUID-05A47015-EBDE-4BE3-B4DA-60BA37437FC2 V1 EN
Figure 169:
Authentication Key Generated Dialog Screen
2.
Select
OK
. TCC600 will display the Open File Dialog screen with a default *.xml
file extension.
1VAC388793-MB A
Section 4
TCC600
TCC300
233
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......