7.4
Line drop compensation
Voltage Regulation Without LDC
When the control is just used to regulate the voltage on the regulator low-side bus, the only
input required is voltage from a line-to-line or line-to-ground VT with a nominal 120 Vac
secondary.
Voltage Regulation With LDC
When it is desirable to regulate the voltage at some distance from the voltage regulator, or
in general to raise the voltage during high load conditions, the Line Drop Compensation
(LDC) feature is used.
Two different LDC methods are available in the TCC300 Digital Tapchanger Control. A
selection in the Setpoints/General section allows the user to select from either Resistance/
Reactance (R/X) or LDC-Z.
1VAC388793-MB A
Section 7
Setpoints
TCC300
513
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......