240 degrees
270 degrees
300 degrees
330 degrees
Aux Current Transformer Units Display
200 mA [200 mA]
1 Amp
5 Amp
VT Configuration
Line to Line
Line to Ground [Line
to Ground]
VT/CT Source
VT Source Correction
-15.0 to +15.0 (V) [0.0]
(_______________)
CT/VT Source Phasing
0 degree [0 degree]
30 degrees
60 degrees
90 degrees
120 degrees
150 degrees
180 degrees
210 degrees
240 degrees
270 degrees
300 degrees
330 degrees
Raise/Lower Output Contacts
Continuous
[Continuous]
Pulsed
Pulse Width
0.2 to 12.0 (sec) [1.5]
(_______________)
Motor Current Settings
Peak Rms Current
110 to 200 (%) [110]
(_______________)
Average Rms Current
110 to 200 (%) [110]
(_______________)
Average Duration
110 to 200 (%) [110]
(_______________)
Program Alarm Relay Mode
Normal [Normal]
Deadman Out
Low Current Block
Disable [Disable]
Enable
Section 11
1VAC388793-MB A
Appendix B Setpoint, Configuration and Communication Record Forms
658
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......