Section 7
Setpoints
7.1
Setpoint profiles
7.1.1
Editing of setpoint profiles
Editing setpoints is accomplished only when the specific setpoint profile has been selected
for editing in TCC600® or the HMI. The following setpoint categories are included in the
four setpoint profiles:
•
Common Settings
•
Power Flow Forward
•
Power Flow Reverse
•
Voltage Reduction
•
Limits
•
VAr Bias
In TCC600 the setpoint profiles are identified by Tabs on the Setpoints dialog screen. In
the HMI, the Common Settings, Power Flow Forward, Power Flow Reverse, Voltage
Reduction, Limits, and VAr Bias submenu headers indicate in the upper right hand corner
the setpoint profile that is being edited.
If a specific setpoint profile has not been previously selected for editing, then the number
in the submenu header will indicate the Active Setpoint Profile. After changing the active
setpoint profile the user must exit the Profile Settings sub header for approximately 1
minute to see the Active Setpoint Profile change indicated in the setpoints sub header.
The control will immediately respond to the new Active Setpoint Profile
settings.
1VAC388793-MB A
Section 7
Setpoints
TCC300
489
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......