character and continue without attempting to resynchronize. Factory setting is 50 msec;
range is 0-32000 msec.
10.2.6
Utilities
10.2.6.1
Calibration-Test
Bias Voltage
Status/Test Mode
When ENT is pressed, the control status can be checked, and a bias test voltage can be
entered to test the control’s automatic operation.
Load Voltage
XXX.X Volts
Displays the real-time measured value of voltage at the regulator or the transformer,
including the voltage reduction if applicable and any corrections made using the user-
selected VT correction voltage.
Voltage Offset
X
Voltage calibration count offset from ADC reference value.
[5]
Volt Cal Coefficient
32767 X
Voltage calibration factor.
[5]
Volt RMS Coefficient
32762 X
Voltage RMS calibration factor.
[5]
Control Load I
x.x mA Lag
Displays the real-time measured value of load current related to the scaling factor Current
Transformer of 200 mA, 1 A or 5A.
[5] Requires Level 3 Access to change.
Section 10
1VAC388793-MB A
Appendix A HMI
650
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......