total record before re-arming for the next record. For example, a setting of 80% will
result in a record with 20% pre trigger data, and 80% post-trigger data.
•
Inputs and Outputs – The recorder can be triggered remotely through serial
communications using TCC600, or automatically, using programmed status signals.
Table 54:
Recorder Partitions and Cycles for 16 Samples/Cycle
Number of partitions
Cycles per partition
1
1365
2
910
3
682
4
546
5
455
6
390
7
341
8
303
9
273
10
248
11
227
12
210
13
195
14
182
15
170
16
160
5.2.1
Setting up the oscillograph recorder
Communication must be established with the target control for this
procedure. When not connected to the control, the Send selection does not
save the Oscillograph Recorder settings to an open file.
1.
From the TCC600® Main Screen menu, select
Setup/Oscillograph/Setup
.
TCC600 will display the Oscillograph Setup dialog screen.
Section 5
1VAC388793-MB A
System setup
266
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......