Table 69:
Requirements for the power converter
Description
Value
Temperature
–40° C to + 80° C
IEC 60068‑2‑1 Cold, –40° C for 96 hours
IEC 60068‑2‑2 Dry Heat, +80° C for 96 hours
IEC 60068‑2‑3 Damp Heat, +40° C @ 95% RH for 96
hours
Transient Protection
High Voltage – All input and output terminals will
withstand 1500 Vac rms to chassis or instrument
ground for one minute with a leakage current not to
exceed 25 mA, for all terminals to ground. Input and
output circuits are electrically isolated from each
other, from other circuits and from ground.
Surge Withstand Capability
IEEE C37.90.1‑2002 2,500 Vpk-pk Oscillatory 4,000
Vpk Fast Transient Burst
IEEE C37.90.1-1989 2,500 Vpk-pk Oscillatory 5,000
Vpk Fast Transient
Radiated Electromagnetic Withstand Capability
All units are protected against electromagnetic
radiated interference from portable communications
transceivers.
Electrostatic Discharge Test
EN 60255‑22‑2‑1997 (EN61000‑4‑2)
Class 4 (8 Kv) – Point Contact Discharge, (15 Kv) –
Air Discharge
Fast Transient Disturbance Test
EN 60255‑22‑4‑2002 (EN61000‑4‑4)
Class A (4 Kv, 2.5 kHz)
1VAC388793-MB A
Section 8
Installation
TCC300
571
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......