Figure 124:
Master/Follower Configuration Dialog Screen
Table 37:
Delta VAr Peer to Peer Options
Item
Description
Sensitivity
Adjustable from -4 to +4 in 0.1 increments with a
factory setting of 0.0.
Circulating Current Limit (Reactive)
Adjustable from 5 mA to 200 mA in 1.0 increments
with a factory setting of 200 mA.
Number of Devices
The number of total devices that are in the paralleling
scheme (maximum 16 inclusive of the Initiator).
Paralleling Address
The unique address for each device (Range 1 – 16).
Peer to Peer Update Speed (in milliseconds)
The time period allocated to read all the paralleled
units relevant data, make the necessary calculations
and disseminate paralleling driven updates to the
system (Range 1000 to 10000).
MVA Rating
The MVA rating of the transformer (Range 1.0 to
1000.0).
Peer to Peer Current Multiplier Correction
A scaling factor to compensate Delta Vars
Calculation, if the CT value is not in the ratio to the
MVA rating (Range 20 to 500 %).
Table continues on next page
1VAC388793-MB A
Section 4
TCC600
TCC300
189
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......