4.
Press the Down arrow pushbutton, as necessary, until the "Current Multiplier"
screen is displayed.
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
CT Multiplier
6000 X C
6.
Utilizing the arrow pushbuttons enter the desired Current Multiplier value from 1 to
32600, then press the ENT pushbutton.
6.2.7.3
Setting the Voltage and Current Multipliers from TCC600
1.
Select
Setup/Configuration
from the TCC600 toolbar. TCC600 will display the
Configuration dialog screen.
GUID-6C74AD06-67C3-433B-B783-6A218088FA6D V1 EN
Figure 290:
Configuration Dialog Screen
2.
Enter the Current, Voltage, Voltage Source and Normalizing Voltage Multipliers.
3.
Select
Save
. TCC600 will display a "Confirm Writing to Device" confirmation
screen.
Section 6
1VAC388793-MB A
Configuration
362
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......