NONSEQ INPUT
Allows the non-sequential input to be used as the Non-Sequential Input or as a SCADA
Cutout input. When SCADA Cutout is selected, all nonsequential functions are disabled.
Factory setting is Non-Sequential.
Input Selection 3
VOLTAGE RED 2
Allows VR2 Input to be used as an Aux Status Input that can be read via DNP or
MODBUS®.
10.2.4.7
Mtr Current Profile
Peak RMS % Change
xxx
Setting for Peak RMS current programmable from 110% to 200% of the stored Peak RMS
current to activate an alarm.
Average RMS % Change
xxx
Setting for Average RMS current programmable from 110% to 200% of the stored
Average RMS current to activate an alarm.
Duration % Change
xxx
Setting for Duration current programmable from 110% to 200% of the stored Duration
current to activate an alarm.
Init. Motor Current
Press ENT to reset.
Reset all Motor Current Profiles and initiate the "Training Mode".
10.2.4.8
CBEMA Setup
Normal Voltage
xxx.x Volts
1VAC388793-MB A
Section 10
Appendix A HMI
TCC300
633
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......