GUID-64E3E9D7-7F66-4451-906E-B934BF7F9785 V1 EN
Figure 428:
Save to Device Confirmation Screen
4.
Select
OK
. TCC600 will display a "Setpoints Successfully Written to Control"
confirmation screen.
GUID-F30E8D82-95A5-4460-AAEE-BBCD9FAD3FEB V1 EN
Figure 429:
Setpoints Successfully Written To The Control Confirmation
Screen
7.8
VAr bias
This feature is intended for but not restricted to use with distribution feeders which have
switched capacitor banks controlled by ABB Autodaptive® Capacitor Controls.
The use of VAr Bias allows the TCC300 Tapchanger Control to coordinate its operation
with Autodaptive Capacitor Control devices on the distribution system in order to
minimize losses, subsequent voltage variations, and equipment capacity requirements of
transmitting VArs. This function is enabled through TCC600® Communications
Software or from the control HMI.
The VAr Bias feature includes two selectable VAr Bias methods, "Step" and "Linear".
When enabled in either "Step or "Linear" mode, the control will bias the Bandcenter based
on the amount of measured reactive load current.
1VAC388793-MB A
Section 7
Setpoints
TCC300
539
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......