purchased the maximum number of IEC 61850 connections is four. The port supports
DHCP protocol and also allows manual configuration of the Ethernet port. MODBUS
protocol "Port Number" and DNP Protocol "Port Number" are required for manual
configuration.
If no communication activity is detected on a previously open ethernet socket, for the
amount of time specified by the "Keepalive Time" setting, the control will then close the
socket and make it available for future connection.
Keepalive Time applies only to Ethernet communication.
5.9.1
Configuring Ethernet port from TCC600
Manual configuration of the Ethernet Port (not enabling DHCP Protocol)
requires that the IP Address, Net Mask and Gateway settings be obtained
from the System Administrator.
1.
Ensure the following conditions exist:
•
The control is energized
•
TCC600® is installed on the host computer
•
The host computer is physically connected to the target control through either
a USB, Serial Port or Modem connection
•
The host computer and the control are physically connected to the target
Ethernet network
2.
Start the TCC600 program. TCC600 will display the TCC600
Main
dialog screen.
3.
Select
Connect/USB, Com Port or Modem
from the Connect dropdown menu.
TCC600 will display the appropriate Connection Dialog Screen.
4.
Enter a valid Level 2 Access Code (if enabled), then select Connect, TCC600 will
attempt to connect to the target control.
5.
If TCC600 returns a Failed to Connect Error screen, repeat Steps 3 and 4.
6.
Level 2 Access if enabled is necessary to complete the Ethernet Port configuration.
If an invalid Access Code was entered, TCC600 will display the connected version
of the TCC600 main screen with either "Read-Only" or "Level 1" access. Disconnect
from the control and repeat Step 4.
7.
If Level Access is not active or a valid Level 2 Access Code was entered, TCC600
will briefly display the "Successfully Connected Level 2" screen and then display
the connected version of the TCC600 Main Screen with Level 2 Access.
8.
From the
Communication
drop-down menu, select
Setup/Ethernet Settings
.
TCC600 will then display the Setup Ethernet dialog screen.
1VAC388793-MB A
Section 5
System setup
TCC300
291
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......