GUID-F94E7F6F-8790-48D5-8849-51B45512FDBC V1 EN
Figure 121:
Reverse Power Vendor Cross Reference Table
4.10.5.4
Configuration
Table 27:
Primary
Item
Description
Voltage Multiplier
Adjustable from 0.1 to 3260.0 in 0.1 increments with
a factory setting of 60.0. User selection must include
knowledge of VT ratio and sensing VT-ratio
correction.
Voltage Source Multiplier
Adjustable from 0.1 to 3260.0 in 0.1 increments with
a factory setting of 60.0. User selection must include
knowledge of source VT ratio and sensing source
VT-ratio correction.
Current Multiplier
Adjustable from 1 to 32600 in 1 increments with a
factory setting of 6000. User selection must include
knowledge of CT ratio, from primary rating to 0.2 A
rating of control.
Primary Power Display
Toggles between two modes of operation: Single-
Phase – based on measured inputs, and Three-
Phase – based on measured inputs and presumed
balanced system. Factory setting is single-phase.
Section 4
1VAC388793-MB A
TCC600
184
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......