GUID-8C5481C0-365B-4398-B96B-245B6558B9F0 V1 EN
Figure 55:
Access Level Code Dialog Screen
2.
Enter a valid Level 2 Access Code, then select OK. TCC600 will display the Access
Granted Successfully confirmation screen.
GUID-75008FE6-45FF-41FE-8C8F-00FD57F9CA77 V1 EN
Figure 56:
Access Granted Successfully Confirmation Screen
3.
Select OK. TCC600 will display the Master/Follower Configuration Tool dialog
screen.
GUID-A4EA0D98-BFCB-4E3B-BBF5-327A050956CE V1 EN
Figure 57:
Master/Follower Configuration Tool Dialog Screen
4.
Select the desired control to be reset, then select "Alarm Reset" to reset the Master/
Follower Lockout Alarm.
Section 3
1VAC388793-MB A
Operation
116
TCC300
User Manual