Tapchanger Type
3.
Press the Right or Left arrow pushbutton, as necessary, to navigate to the
"Nameplate" menu.
4.
Press the Down arrow pushbutton, as necessary, until the "Aux Current
Transformer" screen is displayed.
5.
Press the ENT pushbutton. If prompted, enter a valid Level 2 Access Code. The
following will be displayed:
Aux Curr Transformer
200 mA C
6.
Utilizing the arrow pushbuttons, enter the desired Aux Current Transformer units
display (200 mA, 1 Amp or 5 Amps), then press the ENT pushbutton.
6.2.10.2
Setting Auxiliary Current Transformer Units Display from TCC600
1.
Select
Setup/Configuration
from the TCC600 toolbar. TCC600 will display the
Configuration dialog screen.
GUID-6C74AD06-67C3-433B-B783-6A218088FA6D V1 EN
Figure 302:
Configuration Dialog Screen
2.
From the "VT/CT Load/Aux Current Transformer" section of the dialog screen
select either "200 mA, 1 Amp or 5 Amps".
3.
Select
Save
. TCC600 will display a "Confirm Writing to Device" confirmation
screen.
Section 6
1VAC388793-MB A
Configuration
372
TCC300
User Manual
Содержание TCC300
Страница 1: ...Digital Tapchanger Control TCC300 User Manual ...
Страница 2: ......
Страница 3: ...Document ID 1VAC388793 MB Issued 2016 08 10 Revision A Copyright 2016 ABB All rights reserved ...
Страница 22: ...Updating data file remotely 700 Section 16 Glossary 705 Table of contents 16 TCC300 User Manual ...
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 91: ...1VAC388793 MB A Section 3 Operation TCC300 85 User Manual ...
Страница 126: ...120 ...
Страница 176: ...Section 4 1VAC388793 MB A TCC600 170 TCC300 User Manual ...
Страница 260: ...254 ...
Страница 328: ...322 ...
Страница 494: ...488 ...
Страница 556: ...550 ...
Страница 580: ...574 ...
Страница 600: ...594 ...
Страница 700: ...694 ...
Страница 710: ...704 ...
Страница 712: ...706 ...
Страница 713: ...707 ...
Страница 714: ......
Страница 715: ......