![ABB RELION Series Скачать руководство пользователя страница 82](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191082.webp)
Name
Type
Values (Range)
Unit
Description
Voltage U31B
FLOAT32
0.000...4.000
xUn
Phase C to phase A
voltage (b)
Voltage UoB
FLOAT32
0.000...4.000
xUn
Residual voltage (b)
Voltage Zro-SeqB
FLOAT32
0.000...4.000
xUn
Zero sequence voltage
(b)
Voltage Ps-SeqB
FLOAT32
0.000...4.000
xUn
Positive sequence
voltage (b)
Voltage Ng-SeqB
FLOAT32
0.000...4.000
xUn
Negative sequence
voltage (b)
PTTR thermal level
FLOAT32
0.00...99.99
PTTR calculated
temperature of the
protected object relative
to the operate level
PDNSPTOC1 rat.
I2/I1
FLOAT32
0.00...999.99
%
PDNSPTOC1 ratio I2/I1
Frequency
FLOAT32
30.00...80.00
Hz
Frequency
Frequency gradient
FLOAT32
-10.00...10.00
Hz/s
Frequency gradient
Conductance Yo
FLOAT32
-1000.00...1000.
00
mS
Conductance Yo
Susceptance Yo
FLOAT32
-1000.00...1000.
00
mS
Susceptance Yo
Angle Uo - Io
FLOAT32
-180.00...180.00
deg
Angle residual voltage -
residual current
Angle U23 - IL1
FLOAT32
-180.00...180.00
deg
Angle phase B to phase C
voltage - phase A current
Angle U31 - IL2
FLOAT32
-180.00...180.00
deg
Angle phase C to phase A
voltage - phase B current
Angle U12 - IL3
FLOAT32
-180.00...180.00
deg
Angle phase A to phase B
voltage - phase C current
Angle UoB - IoB
FLOAT32
-180.00...180.00
deg
Angle residual voltage -
residual current (b)
Angle U23B - IL1B
FLOAT32
-180.00...180.00
deg
Angle phase B to phase C
voltage - phase A current
(b)
Angle U31B - IL2B
FLOAT32
-180.00...180.00
deg
Angle phase C to phase A
voltage - phase B current
(b)
Angle U12B - IL3B
FLOAT32
-180.00...180.00
deg
Angle phase A to phase B
voltage - phase C current
(b)
3.8
Nonvolatile memory
The relay does not include any battery backup power. If the auxiliary power is lost,
critical information such as relay configuration and settings, events, disturbance
recordings and other critical data are saved to the relay’s nonvolatile memory. The
relay’s real-time clock keeps running via a 48-hour capacitor backup.
Section 3
1MRS758755 A
Basic functions
76
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...