Parameter
Values (Range)
Unit
Step
Default
Description
R0 line section A
0.000...1000.000
ohm / pu
0.001
4.000
Zero sequence line resistance, line
section A
X0 line section A
0.000...1000.000
ohm / pu
0.001
4.000
Zero sequence line reactance, line
section A
Line Len section A
0.000...1000.000
pu
0.001
0.000
Line length, section A
Table 523:
SCEFRFLO Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
High alarm Dis limit
0.000...1.000
pu
0.001
0.000
High alarm limit for calculated distance
Low alarm Dis limit
0.000...1.000
pu
0.001
0.000
Low alarm limit for calculated distance
Equivalent load Dis
0.00...1.00
0.01
0.50
Equivalent load distance when EF
algorithm equals to load modelling
R1 line section B
0.000...1000.000
ohm / pu
0.001
1.000
Positive sequence line resistance, line
section B
X1 line section B
0.000...1000.000
ohm / pu
0.001
1.000
Positive sequence line reactance, line
section B
R0 line section B
0.000...1000.000
ohm / pu
0.001
4.000
Zero sequence line resistance, line
section B
X0 line section B
0.000...1000.000
ohm / pu
0.001
4.000
Zero sequence line reactance, line
section B
Line Len section B
0.000...1000.000
pu
0.001
0.000
Line length, section B
R1 line section C
0.000...1000.000
ohm / pu
0.001
1.000
Positive sequence line resistance, line
section C
X1 line section C
0.000...1000.000
ohm / pu
0.001
1.000
Positive sequence line reactance, line
section C
R0 line section C
0.000...1000.000
ohm / pu
0.001
4.000
Zero sequence line resistance, line
section C
X0 line section C
0.000...1000.000
ohm / pu
0.001
4.000
Zero sequence line reactance, line
section C
Line Len section C
0.000...1000.000
pu
0.001
0.000
Line length, section C
Table 524:
SCEFRFLO Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Phase voltage Meas
1=Accurate
2=Ph-to-ph without
Uo
1=Accurate
Phase voltage measurement principle
Calculation Trg mode
1=Internal
2=External
2=External
Trigger mode for distance calculation
Section 5
1MRS758755 A
Protection related functions
504
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...