![ABB RELION Series Скачать руководство пользователя страница 491](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191491.webp)
Fault loops “AG Fault” or “BG Fault” or “CG Fault”
Fault loops “AG Fault”, “BG Fault” or “CG Fault” are used for single-phase-to-earth
faults. When the individual earth faults are located at different feeders, they are also
applied in the case of two-phase-to-earth fault. In this case, the phase-to-earth loop
(either “AG Fault” or “BG Fault” or “CG Fault”) corresponding to the faulty phase at
the protected feeder, is used for calculation.
shows the phase-to-earth fault
loop model. The following impedances are measured and stored in the recorded data
of SCEFRFLO.
Flt point resistance
R
fault
=
GUID-2503378E-4AC5-4E9F-9D77-2E7C71592C37 V3 EN
(Equation 46)
Flt loop resistance
R
R
R
N
fault
=
+
+
1
GUID-4DF67AFC-67E4-4BCB-958E-CC9E4872E252 V3 EN
(Equation 47)
Flt loop reactance
X
X
N
=
+
1
GUID-B4E21936-B993-4A8A-9C4A-7425F8AC4670 V3 EN
(Equation 48)
Flt phase reactance
X
=
1
GUID-56EC16DD-7F6A-4DE5-935E-4302196DE21A V3 EN
(Equation 49)
R
1
Estimated positive-sequence resistance from the substation to the fault location
X
1
Estimated positive-sequence reactance from the substation to the fault location
R
0
Estimated zero-sequence resistance from the substation to the fault location
X
0
Estimated zero-sequence reactance from the substation to the fault location
R
N
Estimated the earth return path resistance (= (R0 – R1)/3) from the substation to
the fault location
X
N
Estimated is the earth return path reactance (= (X0 – X1)/3) from the substation to
the fault
R
fault
Estimated fault resistance at the fault location
The recorded data Flt phase reactance provides the estimated positive-sequence
reactance from the substation to the fault location.
1MRS758755 A
Section 5
Protection related functions
REC615 and RER615
485
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...