A070422 V1 EN
Figure 378:
Operating effect of the
BLOCK
input when the selected blocking mode
is "Freeze timer"
If the
BLOCK
input is activated when the operate timer is running, as described in
, the timer is frozen during the time
BLOCK
remains active. If the timer
input is not active longer than specified by the
Reset delay time
setting, the operate
timer is reset in the same way as described in
, regardless of the
BLOCK
input .
The selected blocking mode is "Freeze timer".
11.2
Current based inverse definite minimum time
characteristics
11.2.1
IDMT curves for overcurrent protection
In inverse-time modes, the operation time depends on the momentary value of the
current: the higher the current, the faster the operation time. The operation time
calculation or integration starts immediately when the current exceeds the set
Start
value
and the
START
output is activated.
Section 11
1MRS758755 A
General function block features
712
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...