The function detects the transition from TRUE to FALSE at the
CLK
input. When the
falling edge is detected, the element assigns the
Q
output to TRUE. At the next
execution round, the output is returned to FALSE despite the state of the input.
Signals
Table 103:
F_TRIG Input signals
Name
Type
Default
Description
CLK
BOOLEAN
0
Input signal
Table 104:
F_TRIG Output signal
Name
Type
Description
Q
BOOLEAN
Output signal
Settings
The function does not have any parameters available in LHMI or PCM600.
3.16.1.9
T_POS_XX function blocks
Function block
GUID-4548B304-1CCD-454F-B819-7BC9F404131F V1 EN
Figure 73:
Function blocks
Functionality
The circuit breaker position information can be communicated with the IEC 61850
GOOSE messages. The position information is a double binary data type which is fed
to the POS input.
T_POS_CL and T_POS_OP are used for extracting the circuit breaker status
information. Respectively, T_POS_OK is used to validate the intermediate or faulty
breaker position.
Table 105:
Cross reference between circuit breaker position and the output of the function block
Circuit breaker position Output of the function block
T_POS_CL
T_POS_OP
T_POS_OK
Intermediate '00'
FALSE
FALSE
FALSE
Close '01'
TRUE
FALSE
TRUE
Open '10'
FALSE
TRUE
TRUE
Faulty '11'
TRUE
TRUE
FALSE
Section 3
1MRS758755 A
Basic functions
128
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...