Section 6
Supervision functions
6.1
Trip circuit supervision TCSSCBR
6.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Trip circuit supervision
TCSSCBR
TCS
TCM
6.1.2
Function block
A070788 V1 EN
Figure 262:
Function block
6.1.3
Functionality
The trip circuit supervision function TCSSCBR is designed to supervise the control
circuit of the circuit breaker. The invalidity of a control circuit is detected by using a
dedicated output contact that contains the supervision functionality. The failure of a
circuit is reported to the corresponding function block in the relay configuration.
The function starts and operates when TCSSCBR detects a trip circuit failure. The
operating time characteristic for the function is DT. The function operates after a
predefined operating time and resets when the fault disappears.
The function contains a blocking functionality. Blocking deactivates the
ALARM
output and resets the timer.
6.1.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The
corresponding parameter values are "On" and "Off".
The operation of TCSSCBR can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
1MRS758755 A
Section 6
Supervision functions
REC615 and RER615
509
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...