GUID-718D61B4-DAD0-4F43-8108-86F7B44E7E2D V1 EN
Figure 122:
Operating zones at minimum magnitude levels
Level detector
The measured phase currents are compared phasewise to the set
Start value
. If the
measured value exceeds the set
Start value
, the level detector reports the exceeding of
the value to the phase selection logic. If the
ENA_MULT
input is active, the
Start value
setting is multiplied by the
Start value Mult
setting.
The protection relay does not accept the
Start value
or
Start value Mult
setting if the product of these settings exceeds the
Start value
setting
range.
The start value multiplication is normally done when the inrush detection function
(INRPHAR) is connected to the
ENA_MULT
input.
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
227
Technical Manual