![ABB RELION Series Скачать руководство пользователя страница 425](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191425.webp)
PHPTUV can be used to disconnect from the network devices, such as electric motors,
which are damaged when subjected to service under low voltage conditions.
PHPTUV deals with low voltage conditions at power system frequency. Low voltage
conditions can be caused by:
•
Malfunctioning of a voltage regulator or incorrect settings under manual control
(symmetrical voltage decrease)
•
Overload (symmetrical voltage decrease)
•
Short circuits, often as phase-to-earth faults (unsymmetrical voltage increase).
PHPTUV prevents sensitive equipment from running under conditions that could
cause overheating and thus shorten their life time expectancy. In many cases,
PHPTUV is a useful function in circuits for local or remote automation processes in
the power system.
4.4.2.7
Signals
Table 423:
PHPTUV Input signals
Name
Type
Default
Description
U_A_AB
SIGNAL
0
Phase to earth voltage A or phase to phase voltage
AB
U_B_BC
SIGNAL
0
Phase to earth voltage B or phase to phase voltage
BC
U_C_CA
SIGNAL
0
Phase to earth voltage C or phase to phase voltage
CA
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Table 424:
PHPTUV Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.4.2.8
Settings
Table 425:
PHPTUV Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.05...1.20
xUn
0.01
0.90
Start value
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier in IEC/ANSI IDMT curves
Operate delay time
60...300000
ms
10
60
Operate delay time
Operating curve type
5=ANSI Def. Time
15=IEC Def. Time
21=Inv. Curve A
22=Inv. Curve B
23=Programmable
15=IEC Def. Time
Selection of time delay curve type
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
419
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...