![ABB RELION Series Скачать руководство пользователя страница 315](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191315.webp)
Parameter
Values (Range)
Unit
Step
Default
Description
-23=Recloser E
(132)
-24=Recloser F
(163)
-25=Recloser G
(121)
-26=Recloser H
(122)
-27=Recloser J
(164)
-28=Recloser Kg
(165)
-29=Recloser Kp
(162)
-30=Recloser L
(107)
-31=Recloser M
(118)
-32=Recloser N
(104)
-33=Recloser P
(115)
-34=Recloser R
(105)
-35=Recloser T
(161)
-36=Recloser V
(137)
-37=Recloser W
(138)
-38=Recloser Y
(120)
-39=Recloser Z
(134)
Operate delay time
50...200000
ms
10
50
Operate delay time
Characteristic angle
-179...180
deg
1
-90
Characteristic angle
Max forward angle
0...180
deg
1
80
Maximum phase angle in forward
direction
Max reverse angle
0...180
deg
1
80
Maximum phase angle in reverse
direction
Min forward angle
0...180
deg
1
80
Minimum phase angle in forward direction
Min reverse angle
0...180
deg
1
80
Minimum phase angle in reverse direction
Voltage start value
0.010...1.000
xUn
0.001
0.010
Voltage start value
Table 338:
FDEFLPDEF Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset curve type
Operation mode
1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
1=Phase angle
Operation criteria
Enable voltage limit
0=False
1=True
1=True
Enable voltage limit
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
309
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...