Result quality indicator
The quality of the estimated fault distance is judged and reported in recorded data as
the Flt Dist quality together with the fault distance estimate. The Flt Dist quality is a
bit vector indicating detected sources of inaccuracy in the fault distance estimate. In
case Flt Dist quality equals 1, the result is not affected by error sources. This results
in good quality for fault distance estimate. If factors affecting negatively to fault
distance estimation are detected, the Flt Dist quality is according to
. In this
case estimated fault distance, Flt distance value is given in HMI in parenthesis.
Table 514:
Fault distance quality indicator Flt Dist quality
Value
Corresponding inaccuracy description
2
Estimation stability criterion has not been reached
4
Fault point resistance exceeds 500 Ω
8
Fault point resistance exceeds 5 × X
loop
1)
16
Fault point resistance exceeds 20 × X
loop
1)
32
Flt to Lod Cur ratio is below 1.00
64
Fault distance estimate outside tolerances (<-0.1
pu or >1.1 pu)
128
Distance estimate calculation is not done due to
too low magnitudes of I or U
256
Distance estimate calculation cannot be
performed (for example avoiding internal division
by zero)
1) Xloop is the total loop reactance according to settings
For example, if fault point resistance exceeds 500 Ω and Flt to Lod Cur ratio is below
1.0, Flt Dist quality is “36”. As another example, if no error sources are found, but
stability criterion is not met, the value of Flt Dist quality is “2”.
Impedance settings
The fault distance calculation in SCEFRFLO is based on the fault loop impedance
modeling. The fault loop is parametrized with the impedance settings and these can be
set at maximum for three line sections (A, B and C). Each section is enabled by
entering a section length, which differs from zero to settings
Line Len section A
,
Line
Len section B
or
Line Len section C
in the order section A-> section B-> section C.
The earth-fault loops require both positive-sequence and zero-sequence impedances,
for example,
R1 line section A
and
X1 line section A
,
R0 line section A
and
X0 line
section A
. For the short circuit loops, only positive-sequence impedances are needed.
Even these can be omitted in the short circuit loops, if the setting
Enable simple model
equals "TRUE".
If the impedance settings are in use, it is important that the settings closely match the
impedances of used conductor types. The impedance settings are given in primary
ohms [ohm/pu] and the line section lengths in per unit [pu]. Thus, impedances can be
Section 5
1MRS758755 A
Protection related functions
492
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...