Figure 149:
Configurable operating sectors in phase angle characteristic
Table 325:
Momentary operating direction
Fault direction
The value for DIRECTION
Angle between the polarizing and operating
quantity is not in any of the defined sectors.
0 = unknown
Angle between the polarizing and operating
quantity is in the forward sector.
1= forward
Angle between the polarizing and operating
quantity is in the reverse sector.
2 = backward
Angle between the polarizing and operating
quantity is in both the forward and the reverse
sectors, that is, the sectors are overlapping.
3 = both
If the
Allow Non Dir
setting is "False", the directional operation (forward, reverse) is
not allowed when the measured polarizing or operating quantities are invalid, that is,
their magnitude is below the set minimum values. The minimum values can be defined
with the settings
Min operate current
and
Min operate voltage
. In case of low
magnitudes, the
FAULT_DIR
and
DIRECTION
outputs are set to 0 = unknown,
except when the
Allow non dir
setting is "True". In that case, the function is allowed
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
295
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...