deactivated. The timer calculates the start duration value START_DUR, which
indicates the percentage ratio of the start situation and the set operation time. The
value is available in the monitored data view.
Blocking logic
There are three operation modes in the blocking function. The operation modes are
controlled by the
BLOCK
input and the global setting in
Configuration/System/
Blocking mode
which selects the blocking mode. The
BLOCK
input can be controlled
by a binary input, a horizontal communication input or an internal signal of the
protection relay's program. The influence of the
BLOCK
signal activation is
preselected with the global setting
Blocking mode
.
The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode,
the operate timer is frozen to the prevailing value, but the
OPERATE
output is not
deactivated when blocking is activated. In the "Block all" mode, the whole function is
blocked and the timers are reset. In the "Block OPERATE output" mode, the function
operates normally but the
OPERATE
output is not activated.
4.2.4.5
Neutral admittance characteristics
The applied characteristic should always be set to cover the total admittance of the
protected feeder with a suitable margin. However, more detailed setting value
selection principles depend on the characteristic in question.
The settings defining the admittance characteristics are given in
primary milliSiemens.
The forward and reverse boundary settings should be set so that the forward setting is
always larger than the reverse setting and that there is space between them.
Overadmittance characteristic
The overadmittance criterion is enabled with the setting
Operation mode
set to "Yo".
The characteristic is a circle with the radius defined with the
Circle radius
setting. For
the sake of application flexibility, the midpoint of the circle can be moved away from
the origin with the
Circle conductance
and
Circle susceptance
settings. Default values
for
Circle conductance
and
Circle susceptance
are 0.0 mS, that is, the characteristic
is an origin-centered circle.
Operation is achieved when the measured admittance moves outside the circle.
The overadmittance criterion is typically applied in unearthed networks, but it can also
be used in compensated networks, especially if the circle is set off from the origin.
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
339
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...