CB1 control logic
GUID-8C90B832-96F9-4E2F-BF1F-5CACEB75E09D V1 EN
Figure 351:
Sub module diagram for CB1 control logic
Operation of the output signals is described in the table.
Table 674:
Operating conditions for output signals of CB1
Output signal
Operation description
Operation type
OPEN_CB1
If bus 1 is faulty and the CB1
position is closed,
OPEN_CB1
is
activated after
CB1 Trip delay
has expired.
Protection
Setting
Main bus priority = “bus
2”.
If CB1 position is closed and bus
2 is healthy,
OPEN_CB1
is
activated after
Open CB1 delay
has expired.
Automatic reconnection
CLOSE_CB1
Setting
Main bus priority = “bus
1”.
If both CB1 and CB2 are open,
and bus 1 is healthy,
CLOSE_CB1
is activated after
Close CB1 delay has expired.
Operation is independent of the
state on bus 2.
Automatic reconnection
Setting
Main bus priority = “bus
2”.
If both CB1 and CB2 are open,
bus 2 is faulty and bus 1 is
healthy,
CLOSE_CB1
is
activated after
Close CB1 delay
has expired.
Automatic transfer
Activation of
BLOCK
input deactivates the outputs and resets the timers.
Section 9
1MRS758755 A
Control functions
668
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...