![ABB RELION Series Скачать руководство пользователя страница 268](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191268.webp)
4.1.4.7
Settings
Table 279:
PHPTUC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Current block value
0.00...0.50
xIn
0.01
0.10
Low current setting to block internally
Start value
0.01...1.00
xIn
0.01
0.50
Current setting to start
Operate delay time
50...200000
ms
10
2000
Operate delay time
Table 280:
PHPTUC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Operation mode
1=Three Phase
2=Single Phase
1=Three Phase
Number of phases needed to start
Table 281:
PHPTUC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
4.1.4.8
Monitored data
Table 282:
PHPTUC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
PHPTUC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.1.4.9
Technical data
Table 283:
PHPTUC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the current
measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Start time
Typically <55 ms
Reset time
<40 ms
Reset ratio
Typically 1.04
Retardation time
<35 ms
Operate time accuracy in definite time mode
mode ±1.0% of the set value or ±20 ms
Section 4
1MRS758755 A
Protection functions
262
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...