Average calculation
VSQVUB calculates two sets of measured voltage unbalance values, a three-second
and a ten-minute non-sliding average value. The three-second average value is used
for continuous monitoring. The ten-minute average is used for percentile calculation
for a longer period.
The Average calculation module uses five different methods for the average
calculation. The required method can be selected with the
Unb detection method
parameter.
When the "Neg Seq" mode is selected with
Unb detection method
, the voltage
unbalance is calculated based on the negative-sequence voltage magnitude. Similarly,
when the "Zero Seq" mode is selected, the voltage unbalance is calculated based on
the zero-sequence voltage magnitude. When the "Neg to Pos Seq" mode is selected,
the voltage unbalance is calculated based on the ratio of the negative-sequence voltage
magnitude to the positive-sequence magnitude. When the "Zero to Pos Seq" mode is
selected, the voltage unbalance is calculated based on the ratio of the zero-sequence
voltage magnitude to the positive-sequence magnitude. When the "Ph vectors Comp"
mode is selected, the ratio of the maximum phase voltage magnitude deviation from
the mean voltage magnitude to the mean of the phase voltage magnitude is used for
voltage unbalance calculation.
The calculated three-second value and ten-minute value are available in the
Monitored data view through the outputs
3S_MN_UNB
and
10MN_MN_UNB
.
For VT connection = "Delta", the calculated zero-sequence voltage is
always zero, hence, the setting
Unb detection method
= "Zero Seq" is
not applicable in this VT configuration.
Voltage unbalance detector
The three-second average value is calculated and compared to the set value
Unbalance start val
. If the voltage unbalance exceeds this limit, the
MN_UNB_AL
output is activated.
The activation of the
BLOCK
input blocks
MN_UNB_AL
output.
Percentile calculation
The Percentile calculation module performs the statistics calculation for the level of
voltage unbalance value for a settable duration. The operation of the Percentile
calculation module can be described with a module diagram.
Section 10
1MRS758755 A
Power quality measurement functions
700
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...