3.14.5.3
Signals
Table 56:
GOOSERCV_INTL Output signals
Name
Type
Description
POS_OP
BOOLEAN
Position open output signal
POS_CL
BOOLEAN
Position closed output signal
POS_OK
BOOLEAN
Position OK output signal
VALID
BOOLEAN
Output signal
3.14.6
GOOSERCV_CMV function block
3.14.6.1
Function block
GUID-4C3F3A1A-F5D1-42E1-840F-6106C58CB380 V1 EN
Figure 53:
Function block
3.14.6.2
Functionality
The GOOSERCV_CMV function is used to connect GOOSE measured value inputs
to the application. The MAG_IN (amplitude) and ANG_IN (angle) inputs are defined
in the GOOSE configuration (PCM600).
The MAG output passes the received GOOSE (amplitude) value for the application.
Default value (0) is used if VALID output indicates invalid status.
The ANG output passes the received GOOSE (angle) value for the application.
Default value (0) is used if VALID output indicates invalid status.
3.14.6.3
Signals
Table 57:
GOOSERCV_CMV Output signals
Name
Type
Description
MAG
FLOAT32
Output signal (amplitude)
ANG
FLOAT32
Output signal (angle)
VALID
BOOLEAN
Output signal
Section 3
1MRS758755 A
Basic functions
110
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...