Table 597:
FMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Def frequency Sel
1=Nominal
2=Zero
1=Nominal
Default frequency selection
8.1.8.6
Monitored data
Table 598:
FMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
f-Hz
FLOAT32
35.00...75.00
Hz
Measured frequency
F_INST
FLOAT32
35.00...75.00
Hz
Frequency,
instantaneous value
F_DB
FLOAT32
35.00...75.00
Hz
Frequency, reported
value
F_RANGE
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Measured frequency
range
8.1.8.7
Technical data
Table 599:
FMMXU Technical data
Characteristic
Value
Operation accuracy
±10 mHz
(in measurement range 35...75 Hz)
8.1.8.8
Technical revision history
Table 600:
FMMXU Technical revision history
Technical revision
Change
B
Added new setting
Def frequency Sel. Frequency
measurement range lowered from 35 Hz to 10 Hz.
8.1.9
Sequence current measurement CSMSQI
8.1.9.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Sequence current measurement
CSMSQI
I1, I2, I0
I1, I2, I0
1MRS758755 A
Section 8
Measurement functions
REC615 and RER615
575
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...