Functionality
NOT is used to generate combinatory expressions with Boolean variables.
NOT inverts the input signal.
Signals
Table 95:
NOT Input signal
Name
Type
Default
Description
I
BOOLEAN
0
Input signal
Table 96:
NOT Output signal
Name
Type
Description
O
BOOLEAN
Output signal
Settings
The function does not have any parameters available in LHMI or PCM600.
3.16.1.5
MAX3 function block
Function block
GUID-5454FE1C-2947-4337-AD58-39D266E91993 V1 EN
Figure 69:
Function block
Functionality
The maximum function MAX3 selects the maximum value from three analog values.
Disconnected inputs and inputs whose quality is bad are ignored. If all inputs are
disconnected or the quality is bad, MAX3 output value is set to -2^21.
Signals
Table 97:
MAX3 Input signals
Name
Type
Default
Description
IN1
FLOAT32
0
Input signal 1
IN2
FLOAT32
0
Input signal 2
IN3
FLOAT32
0
Input signal 3
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
125
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...