GUID-17E4650D-ADFD-408E-B699-00CBA1E934B8 V1 EN
Figure 215:
Behavior of different IDMT reset modes. Operate signal is based on
settings Type of reset curve = “Def time reset” and Type of time
reset= “Freeze Op timer”. The effect of other reset modes is also
presented
The
Time multiplier
setting is used for scaling the IDMT operate times.
The
Minimum operate time
setting parameter defines the minimum desired operate
time for IDMT. The setting is applicable only when the IDMT curves are used.
The
Minimum operate time
setting should be used with care because
the operation time is according to the IDMT curve, but always at least
the value of the
Minimum operate time
setting. For more information,
see the
IDMT curves for overcurrent protection
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
417
Technical Manual