Table 441:
NSPTOV Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.4.4.7
Settings
Table 442:
NSPTOV Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.010...1.000
xUn
0.001
0.030
Start value
Operate delay time
40...120000
ms
1
40
Operate delay time
Table 443:
NSPTOV Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 444:
NSPTOV Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
4.4.4.8
Monitored data
Table 445:
NSPTOV Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
NSPTOV
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
429
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...