3.16.11.10
Monitored data
Table 175:
Monitored data
Name
Type
Values (Range)
Unit
Description
Command response
Enum
0=No commands
1=Select open
2=Select close
3=Operate open
4=Operate close
5=Direct open
6=Direct close
7=Cancel
8=Position
reached
9=Position
timeout
10=Object status
only
11=Object direct
12=Object select
13=RL local
allowed
14=RL remote
allowed
15=RL off
16=Function off
17=Function
blocked
18=Command
progress
19=Select
timeout
20=Missing
authority
21=Close not
enabled
22=Open not
enabled
23=Internal fault
24=Already
close
25=Wrong client
26=RL station
allowed
27=RL change
28=Abortion by
trip
Latest command
response
LR state
Enum
0=Off
1=Local
2=Remote
3=Station
4=L+R
5=L+S
6=L+S+R
7=S+R
LR state monitoring
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
161
Technical Manual