boundary line counterclockwise from the vertical axis. A positive
Susceptance tilt
Ang
value rotates the oversusceptance boundary line counterclockwise from the
horizontal axis.
In case of the non-directional conductance and susceptance criteria, the
Conductance
reverse
setting must be set to a smaller value than
Conductance forward
and the
Susceptance reverse
setting must be set to a smaller value than
Susceptance forward
.
Operation is achieved when the measured admittance moves outside the
characteristic.
The combined overconductance and oversusceptance criterion is applicable in high-
resistance earthed, unearthed and compensated networks or in the systems where the
system earthing may temporarily change during normal operation from compensated
to unearthed system.
GUID-1A21391B-A053-432B-8A44-7D2BF714C52D V2 EN
Figure 177:
Combined forward directional overconductance and forward
directional oversusceptance characteristic. Left figure: the
Conductance tilt Ang and Susceptance tilt Ang settings equal zero
degrees. Right figure: the setting Conductance tilt Ang > 0 degrees
and the setting Susceptance tilt Ang < 0 degrees.
Section 4
1MRS758755 A
Protection functions
344
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...