![ABB RELION Series Скачать руководство пользователя страница 411](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191411.webp)
Table 405:
PDNSPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 406:
PDNSPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Min phase current
0.05...0.30
xIn
0.01
0.10
Minimum phase current
4.3.2.8
Monitored data
Table 407:
PDNSPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
RATIO_I2_I1
FLOAT32
0.00...999.99
%
Measured current ratio
I2 / I1
PDNSPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.3.2.9
Technical data
Table 408:
PDNSPTOC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
±2% of the set value
Start time
<70 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
405
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...