6.2.8
Monitored data
Table 541:
SEQSPVC Monitored data
Name
Type
Values (Range)
Unit
Description
SEQSPVC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
6.2.9
Technical data
Table 542:
SEQSPVC Technical data
Characteristic
Value
Operate time
1)
NPS function
U
Fault
= 1.1 × set
Neg
Seq voltage Lev
<33 ms
U
Fault
= 5.0 × set
Neg
Seq voltage Lev
<18 ms
Delta function
ΔU = 1.1 × set
Voltage
change rate
<30 ms
ΔU = 2.0 × set
Voltage
change rate
<24 ms
1) Includes the delay of the signal output contact, f
n
= 50 Hz, fault voltage with nominal frequency injected
from random phase angle, results based on statistical distribution of 1000 measurements
6.3
Runtime counter for machines and devices MDSOPT
6.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Runtime counter for machines and
devices
MDSOPT
OPTS
OPTM
6.3.2
Function block
GUID-C20AF735-FF25-411B-9EA6-11D595484613 V3 EN
Figure 274:
Function block
Section 6
1MRS758755 A
Supervision functions
526
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...