minimum or maximum magnitude corresponding to swell or dip/interruption during
variation is temporarily stored. If the minimum or maximum is found in tracking and
a new magnitude is stored, also the inactive phase voltages are stored at the same
moment, that is, the inactive phases are not magnitude-tracked. The time instant (time
stamp) at which the minimum or maximum magnitude is measured is also temporarily
stored for each voltage phase where variation is active. Finally, variation detection
triggers the recorded data update when the variation activation ends and the maximum
duration time is not exceeded.
The data objects to be recorded for PHQVVR are given in
. There are totally
three data banks, and the information given in the table refers to one data bank content.
The three sets of recorded data available are saved in data banks 1-3. The data bank 1
holds always the most recent recorded data, and the older data sets are moved to the
next banks (1→2 and 2→3) when a valid voltage variation is detected. When all three
banks have data and a new variation is detected, the newest data are placed into bank
1 and the data in bank 3 are overwritten by the data from bank 2.
shows a valid recorded voltage interruption and two dips for the
Phase
mode
value "Single Phase". The first dip event duration is based on the
U_A
duration,
while the second dip is based on the time difference between the dip stop and start
times. The first detected event is an interruption based on the
U_B
duration given in
. It is shown also with dotted arrows how voltage time stamps are taken
before the final time stamp for recording, which is shown as a solid arrow. Here, the
U_B
timestamp is not taken when the
U_A
activation starts.
U_A
U_C
U_B
U_A duration
U_B duration
U_B amplitude &
timestamp
U_A amplitude &
timestamp
U_C amplitude & timestamp
Voltage dip set
Voltage swell set
D
ip
st
art
D
ip
st
op
Voltage Int set
GUID-7A859344-8960-4CF3-B637-E2DE6D3BDA85 V1 EN
Figure 369:
Valid recorded voltage interruption and two dips
Section 10
1MRS758755 A
Power quality measurement functions
690
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...