Figure 145:
Definition of the relay characteristic angle, RCA=–90 degrees in an
isolated network
Directional earth-fault protection in an isolated neutral network
In isolated networks, there is no intentional connection between the system neutral
point and earth. The only connection is through the phase-to-earth capacitances (C
0
)
of phases and leakage resistances (R
0
). This means that the residual current is mainly
capacitive and has a phase shift of -90 degrees compared to the polarizing voltage.
Consequently, the relay characteristic angle (RCA) should be set to -90 degrees and
the operation criteria to "IoSin" or "Phase angle". The width of the operating sector in
the phase angle criteria can be selected with the settings
Min forward angle
,
Max
forward angle
,
Min reverse angle
or
Max reverse angle
illustrates a
simplified equivalent circuit for an unearthed network with an earth fault in phase C.
For definitions of different directional earth-fault characteristics, see
Directional earth-fault principles
Section 4
1MRS758755 A
Protection functions
288
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...