Operation mode “Intermittent EF” is dedicated for detecting restriking or intermittent
earth faults. A required number of intermittent earth fault transients set with the
Peak
counter limit
setting must be detected for operation. Therefore, transient faults or
permanent faults with only initial fault ignition transient are not detected in
“Intermittent EF” mode. The application of “Intermittent EF” mode is limited to low
ohmic intermittent or restriking earth faults.
In the “Intermittent EF” mode, the operate timer is started when the following
conditions are met.
•
Transient is detected by the Transient detector (indicated with
PEAK_IND
output)
•
Earth fault is detected by the GFC at time of transient
•
Fault direction equals
Directional mode
setting
•
Estimated stabilized fundamental frequency residual current exceeds the set
Min
operate current
level
When a required number of intermittent earth-fault transients set with the
Peak
counter limit
setting are detected without the function being reset (depends on the
drop-off time set with the
Reset delay time
setting), the
START
output is activated. The
INTR_EF
output is activated to indicate the fault type is intermittent or restriking
earth fault. The operate timer is kept activated as long as transients occur during the
drop-off time defined by setting
Reset delay time
.
The
OPERATE
output is activated when
Operate delay time
has elapsed, required
number of transients has been detected, earth fault is detected by the GFC, fault
direction matches the
Directional mode
setting and estimated stabilized fundamental
frequency residual current exceeds set
Minimum operate current
setting.
The
Reset delay time
starts to elapse from each detected transient. Function is reset if
time between current peaks is more that
Reset delay time
or if the General Fault
Criterion release is reset. After
OPERATE
output activation,
START
and
OPERATE
outputs are reset immediately at the falling edge of General Fault Criterion release,
that is, when zero-sequence voltage falls below
Voltage start value
. This should be
considered if “Intermittent EF" mode is applied in case earth faults are only alarmed
to avoid repetitive start and operate events.
To keep the operate timer activated between current spikes during
intermittent or restriking earth fault,
Reset delay time
should be set to
a value exceeding the maximum expected time interval between
(obtained at full resonance condition). The recommended value is at
least 300 ms.
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
389
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...