Voltage check
The phase voltage magnitude is checked when deciding whether the fuse failure is a
three, two or a single-phase fault.
The module makes a phase-specific comparison between each voltage input and the
Seal in voltage
setting. If the input voltage is lower than the setting, the corresponding
phase is reported to the decision logic module.
Current and voltage delta criterion
The delta function can be activated by setting the
Change rate enable
parameter to
"True". Once the function is activated, it operates in parallel with the negative
sequence-based algorithm. The current and voltage are continuously measured in all
three phases to calculate:
•
Change of voltage dU/dt
•
Change of current dI/dt
The calculated delta quantities are compared to the respective set values of the
Current
change rate
and
Voltage change rate
settings.
The delta current and delta voltage algorithms detect a fuse failure if there is a
sufficient negative change in the voltage amplitude without a sufficient change in the
current amplitude in each phase separately. This is performed when the circuit breaker
is closed. Information about the circuit breaker position is connected to the
CB_CLOSED
input.
There are two conditions for activating the current and voltage delta function.
•
The magnitude of dU/dt exceeds the corresponding value of the
Voltage change
rate
setting and magnitude of dI/dt is below the value of the
Current change rate
setting in any phase at the same time due to the closure of the circuit breaker
(
CB_CLOSED
= TRUE).
•
The magnitude of dU/dt exceeds the value of the
Voltage change rate
setting and
the magnitude of dI/dt is below the
Current change rate
setting in any phase at the
same time and the magnitude of the phase current in the same phase exceeds the
Min Op current delta
setting.
The first condition requires the delta criterion to be fulfilled in any phase at the same
time as the circuit breaker is closed. Opening the circuit breaker at one end and
energizing the line from the other end onto a fault could lead to an improper operation
of SEQSPVC with an open breaker. If this is considered to be an important
disadvantage, the
CB_CLOSED
input is to be connected to FALSE. In this way only
the second criterion can activate the delta function.
The second condition requires the delta criterion to be fulfilled in one phase together
with a high current for the same phase. The measured phase current is used to reduce
the risk of a false fuse failure detection. If the current on the protected line is low, a
voltage drop in the system (not caused by the fuse failure) is not followed by a current
1MRS758755 A
Section 6
Supervision functions
REC615 and RER615
521
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...