8.1.7.5
Monitored data
Table 592:
RESVMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
Uo-kV
FLOAT32
0.00...4.00
xUn
Measured residual
voltage
BLOCK
BOOLEAN
0=False
1=True
Block signal for all binary
outputs
HIGH_ALARM
BOOLEAN
0=False
1=True
High alarm
HIGH_WARN
BOOLEAN
0=False
1=True
High warning
U_INST_RES
FLOAT32
0.00...4.00
xUn
Residual voltage
Amplitude, magnitude of
instantaneous value
U_ANGL_RES
FLOAT32
-180.00...180.00
deg
Residual voltage angle
U_DB_RES
FLOAT32
0.00...4.00
xUn
Residual voltage
Amplitude, magnitude of
reported value
U_DMD_RES
FLOAT32
0.00...4.00
xUn
Demand value of residual
voltage
U_RANGE_RES
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Residual voltage
Amplitude range
8.1.7.6
Technical data
Table 593:
RESVMMXU Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
voltage: f/f
n
= ±2 Hz
±0.5% or ±0.002 × U
n
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
RMS: No suppression
8.1.7.7
Technical revision history
Table 594:
RESVMMXU Technical revision history
Technical revision
Change
B
-
C
Residual voltage angle and demand value added
to Monitored data view
D
Internal improvement
E
Internal improvement
1MRS758755 A
Section 8
Measurement functions
REC615 and RER615
573
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...