Name
Type
Values (Range)
Unit
Description
MAN_CB_CL
BOOLEAN
0=False
1=True
Indicates CB manual
closing during reclosing
sequence
SOTF
BOOLEAN
0=False
1=True
Switch-onto-fault
DARREC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
9.4.10
Technical data
Table 672:
DARREC Technical data
Characteristic
Value
Operate time accuracy
±1.0% of the set value or ±20 ms
9.4.11
Technical revision history
Table 673:
DARREC Technical revision history
Technical revision
Change
B
The
PROT_DISA
output removed and removed
the related settings
C
The default value of the
CB closed Pos status
setting changed from "True" to "False"
D
SHOT_PTR output range 0...7 (earlier 0...6)
E
Monitored data ACTIVE transferred to be ACT
visible output. SHOT_PTR output range 1...7.
F
Internal improvement
9.5
Automatic transfer switch ATSABTC
9.5.1
Identification
Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE
C37.2 device
number
Automatic transfer switch
ATSABTC
ATSABTC
ATSABTC
1MRS758755 A
Section 9
Control functions
REC615 and RER615
665
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...